Series 900 Steam HP Boiler

Series 900 Steam HP Boiler

The Series 900 Steam Boiler is available with firing inputs from 600,000 Btu/hr to 900,000 Btu/hr. However, many millions of Btu’s can be delivered by creating an efficient, fully modular system of multiple vessels properly sequenced by a control panel.

divider

Design

The Series 900 Steam Boiler is manufactured to exceed ASME Section I standards and is capable of providing pressure of up to 125 psi. These vessels contain 73 vertical firetubes, each of which is 1½” diameter, each fitted with a high-efficiency turbulator for maximum heat transfer. The combustion chamber is fully water-backed, with burners that are UL listed. This boiler qualifies as a Category I gas appliance with industry standard controls wired to NEC specifications.

 

Safety

A well-made, heavy vessel is naturally a safer boiler. But Superior Boilers also have a firebox design that is completely backed by water, along with extra safety controls on the boiler that results in a very safe and secure package.

Standard Features

The following standard features include nationally known parts and controls that are available at most supply houses, allowing for quick and easy repair and maintenance, which can dramatically reduce down time:

  • UL Listed Gas Trains and Control Systems.
  • Choice of Power Burners.
  • Main and Auxiliary Gas Valves
  • Air Flow Switch
  • Main Manual Leak Test Valve
  • Pressure Control
  • High-Limit With Manual Reset
  • 5801-30 lb Pressure Gauge
  • Siphon Loops
  • 150 Water Level Control
  • Automatic Low Water Cutoff w/ Manual Reset
  • Gauge Glass Assembly
  • Burner Control Relay
  • Operating Light
  • 1½” Diameter Firetubes of SA178-A Steel
  • Turbulators for Maximum Heat Transfer
  • Two Inches of Insulation With a Painted Steel Jacket.

Support Documents

Cut Sheet (PDF)
Sample Spec (Word Doc)
O&M Manual (PDF)
Steam Lit Piece (PDF)
Steam Boiler Brochure (PDF)

Drawings

Series 900 Steam, High Pressure
Model #
HP
File
GMS-600
13.8
GMS-700
16.2
GMS-800
18.5
GMS-900
23.1

Boiler Efficiencies

Series 900 Steam, High Pressure
Model
Input (BTU/Hr)
Gross OutPut
HP Output
Combustion Efficiency
GPM @ Riseº F
Steam Output (lbs/hr)
GMS-600
600,000
508,800
13.8HP
81%
N/A
478
GMS-700
700,000
589,400
16.2HP
81%
N/A
558
GMS-800
800,000
664,800
18.5HP
81%
N/A
637
GMS-900
900,000
746,100
23.1HP
81%
N/A
717

Boiler Dimensions

Series 900 Steam, High Pressure
Feature
Dimension
Vessel Width
30.5"
Vessel Height
66"
Boiler Weight
800 lbs
Boiler Depth w/ Burner
61"
Gas Inlet Height
12"
Return Water Inlet Height
9"
Height Required at Installation
90"
Clearance to Front of Boiler
48"
Clearance to Side of Boiler
18"
Clearance Between Boilers
6"
Clearance of Steam Pipe to Vessel Top
24"

TOP